Home
Product Center
News
Contact Us
Documents

News 

News

LD-B10-A380 dry-type transformers temperature controller

Publish Date 2022-10-27
1. the main features
▲ with large digital numbers display, so that the working status of thermostats and display
of measured values more intuitive.
▲ adjusted using the I2C and storage technology, data protection save power.
▲ external three-phase fan with fan motivation (regular start and stop) function.
▲ with over temperature alarm, over temperature trip, fan start and stop functions.
▲ with 4-20mA analog current output and RS-485 communication.
2.technical indicators
1, measurement range: 0.0 ~ 200.0 ℃
2, measurement accuracy: ± 1% FS (0.5 thermostat, sensor 0.5)
3, resolution: 0.1 ℃
4, the digital compensation range: -19.9 ℃ ~ +19.9 ℃
5, using the conditions: ambient temperature -20 ~ +55 ℃
Relative humidity <90% (25 ℃)
Supply voltage 380V (+10%, -15%)
Power frequency (50HZ ~ 60HZ) ± 2HZ
6, relay contact outputs: fan contact capacity: 7A/250VAC
Control output capacity: 10A/250VAC; 10A/30VDC
7, temperature controller power consumption: ≤ 15W
8, temperature controller weight: about 2.5kg
9, Overall Dimensions: 260 mm * 196 mm (high * width)
10, hole size: 230 mm * 180 mm (high * width)
Embed Depth: 70mm
11, sensor type: Pt100 (φ4 × 40mm)
12, analog current output: 4 ~ 20mA (linear corresponding to 0.0 ~ 200.0 ℃), the load
resistance ≤ 500Ω
13, Communication: RS-485 communication is connected with RS-485/232 Interface, up to 28 sets of temperature controller connected, communication range up to 1200 meters
14, production standards: JB/T7631-2005 "transformer resistance thermometer"
15, through the certification standards: ISO9001 international quality management system
certification
16, by the test standards: IEC61000-4: 1995 International Standard GB/T17626-1998 "EMC
test and measurement technology" standards
17, through the interference of pilot projects:
1) The common-mode AC 250V (50HZ) or series mode AC 200mV (50HZ) interference
voltage, the display changes less than the basic error.
2) Electrical fast transients: thermostat power cord and input / output terminal can
withstand the frequency 5KHz, voltages were 1KV 2KV and electrical fast transient
test, display and control the absolute value of additional error limits to meet the
standards .
3) Static Interference: 8KV thermostat can withstand electrostatic discharge test, display
and control the absolute value of additional error limits to meet the standards.
4) Space radio frequency interference: thermostat can withstand the frequency of 80 ~
1000MHz, field strength 10V / m electromagnetic field radiation tests, the display and
control the absolute value of additional error limits to meet the standards.
3.Model Example
LD-B10-A380D
LD-B10-A380DC
LD-B10-A380I
LD-B10-A380IC
LD-B10-A380G
LD-B10-A380GC
LD-B10-A380E
LD-B10-A380EI
LD-B10-A380EG
LD-B10-A380EC
LD-B10-A380EIC
LD-B10-A380EGC
LD-B10-A380EF
LD-B10-A380EFI
LD-B10-A380EFG
LD-B10-A380EFC
LD-B10-A380EFIC
LD-B10-A380EFGC
LD-B10-A380F
LD-B10-A380FI
LD-B10-A380FG
LD-B10-A380FC
LD-B10-A380FIC
LD-B10-A380FGC

The above models are some examples. If there are special requirements. Explain before ordering.