1. Introduction
Safe operation and working life of power transformers depends largely on the safety and reliability of transformer winding. If the temperature of transformer winding exceed the temperature which insulation withstand, it will damage the insulation. This is one of the most important reasons that transformers cannot operate normally.
BWDK series temperature controller of dry transformer (Referred to as temperature controller) is an intelligent controller designed especially for safe operation of dry transformer. The temperature controller features adoption of single chip computer technology and utilization of the platinum thermo-resistors embedded in the winding of the dry transformer for detection and display of temperature rise of the transformer windings. It can start or stop the cooling fan automatically for forced air cooling of windings and control over-temperature alarm and over-temperature tripping output so that the transformer will be operated safely.
2. Technical Indicators
2.1 Range of measurement: -30.0℃~240.0℃
2.2 Accuracy of measurement: Grade of accuracy: Grade 1(Grade 0.5 for temperature controller, Grade B for sensor)
Resolution 0.1℃
2.3 Operating conditions: Room temperature: -20℃~55℃
Relative humidity: < 95% (25℃)
Power frequency: 50Hz or 60Hz (±2Hz)
Power voltage: AC220V (+10%, -15%)
Or AC380V (3-phase 3-wire system) (+10%, -15%)
(Power voltage should be indicated before placing order, otherwise AC220V shall govern)
2.4 Power consumption of temperature controller: ≤8W
2.5 Execution standard: Production standard: JB/T7631-2005 Electronic Thermo-controllers for Transformers
Certification passed: ISO9001:2008 Quality Management Systems-requirements
Test passed: IEC61000-4:2002 International Standard and GB/T17626-2008 Standard for Electromagnetic Compatibility Test and Measuring Technology
2.6 Relay contact output:
Capacity of contact of fan: 6A/250VAC (Cosφ=0.4) (Single-phase fan)
9A/380VAC (Cosφ=0.4) (Three-phase fan)
Control of output capacity: 5A/250VAC; 5A/30VDC (Resistance)
2.7 Protection class: IP40
Protection class of panel: IP54
3. Type and Classification of Function
Type Function
Type D
(Ordinary type) Three-phase circular measurement; Three-phase circular display/maximum value display and mutual switching between two functions; Input disconnection and trouble self-check display and output; Auto start and stop of cooling fan and output; Over-temperature alarm display and output; Over-temperature tripping display and output; Display of manual/auto modes of fan, output and mutual switching; Digital compensation for value displayed in each channel; Function of "black box"; Timed start, stop and control function of fan; Detection of output status.
Type E The same as Type D, with addition of 4~20mA analogue current output.
Type F The same as Type D, with addition of RS485 serial communications function.
Type G The same as Type D, with addition of one-way transformer room temperature measurement and control.
Type I The same as Type D, with addition of one-way transformer core temperature measurement and alarm.
Type L The same as Type D, with addition of protection and alarm function for lack of phase and failure of fan.
Type C The same as Type D, with addition of interlock control of Pt100
and PTC on over-temp alarm and over-temp trip signal.
Note: Other special requirements for the temperature controller should be indicated when placing orders. |
|
|
|
Product Image
|